GENERATOR SPECIFICATION
    
Power Rating (KVA) 40
Electric Power (KWe) 32
Rated Current (A) 56
No of Phases/Volts* 3/415
Dimensions (L X W X H, mm x mm x mm) 3100 x 1200 x 1630
Fuel Tank Capacity (Litres) 250
Battery Capacity (AH) 120
System Voltage (VDC) 12
Weight (Kg) 1225
Dry Weight (Engine-Kg) 350
ENGINE SPECIFICATION
Engine Model ALGPWO4DMK1.E4
Engine Max HP 53.5
Engine Rated HP 48.7
Aspiration Natural
No of Cylinders 4
Bore & Stroke (mm x mm) 104 x 118
Displacement (Litres) 4.009
Compression Ratio 17.9:1
Fuels cons (Litre/hr)** 5.6
Lub oil Sumb Capacity (Litres) 7.5
Lub oil Consumption <0.15%
Coolant Capacity (Litres) 15.0
Governing Class A1
* Single Phase DG set is available optional from 10 KVA
** Fuel Consumption of Genset @75% of load is considering specific gravity of fuel 0.8355 at NTP
     condition, Tolerance will be +5%

ALTERNATOR SPECIFICATIONS 

Phase : Three/Single
Frequency,             Hz : 50
Voltage,                   V : 415/240
Power factor,          lag : 0.8
Ambient : 40 deg.c
Altitude : <1000 mtrs.
Speed, rpm : 1500
Mounting : Horizontal foot mounted
Duty : Continuous
Direction of rotation : Clockwise from de
Automatic voltage regulator : M/c mounted
Voltage regulation : +/-1% with 4% prime mover speed variation
Standards : IS 4722 -1992, IEC 34
Class of insulation : H
Temperature rise : H
Enclosure : IP 20
Cooling : IC 01
Wave form distortion (thd) : Less than 3%
Overload capacity : 10% overload for 1hr. once in 12 hrs.
Unbalance permitted : 25% with none of the phase currents exceeding the rated current. Temp   rise limits for corresponding class of insulation may exceed 10 degre c   under such cond. voltage regulation under above condition will not apply.
No. of bearings : Single /Double
Lubrication type : Grease Lubricated


ALTERNATOR FEATURES

•  Compact and aesthetically built.
•  Conforms to all leading industrial and marine standards.
•  Simple design, fewer parts easy access to coupling bolts, output terminals and rotating diodes.
•  Simple to install and maintain.
•  Wide range of flange adopters and single bearing flexi-disc couplings.
•  Wound with 2/3 pitches in stator to eliminate harmonics.
•  Sophisticated and reliable AVR, having good capability to handle non-linear loads.
•  Self lubricating, sealed type for ball bearing.
•  Paralleling operation facility is optional in frame 4AB200 & 4AB225.

POWER RATING

Power rating as per Standard reference condition as per BS 5514/ISO 3046/ISO 8528

Reference condition (Dec C Ambient Temp) 27
Atmospheric Condition (KPA-750mm of Hg) 100
Humidity 60% - As per IS10002, ISO 3046
Our Products
 
     